9.38
1
b
1
b
h
l
1
l
QUICKTRONIC
®
INTELLIGENT DALI DIM –
ECG dimmable for CFL
Product
reference
Product
number
a
T
QTi DALI-T/E 1X18…57 DIM
1)
4008321060808
1xDL 24
1x1200
0.12
26
0,96
+10…+50 154…276
42…130
1xDL 40
1x3500
0.20
45
0,98
+10…+50
1xDT/E 26 CONSTANT
1x1800
0.13
29
0,97
+10…+50
1xDT/E 26
1x1800
0.13
29
0,97
+10…+50
1xDT/E 32 CONSTANT
1x2400
0.16
36
0,98
+10…+50
1xDT/E 32
1x2400
0.16
36
0,98
+10…+50
1xDULUx T/E 42 CONSTANT 1x3200
0.21
47
0,99
+10…+50
1xDT/E 42
1x3200
0.21
47
0,99
+10…+50
QTi DALI-T/E 2X18…42 DIM
1)
4008321060822
2xDL 24
2x1200
0.22
51
0,97
+10…+50 154…276
42…130
2xDL 40
2x3500
0.38
87
0,99
+10…+50
2xDT/E 18
2x1200
0.17
38
0,95
+10…+50
2xDT/E 26 CONSTANT
2x1800
0.25
56
0,98
+10…+50
2xDT/E 26
2x1800
0.25
56
0,98
+10…+50
2xDT/E 32 CONSTANT
2x2400
0.30
69
0,99
+10…+50
2xDT/E 32
2x2400
0.30
69
0,99
+10…+50
2xDULUx T/E 42 CONSTANT 2x3200
0.39
90
0,99
+10…+50
2xDT/E 42
2x3200
0.39
90
0,99
+10…+50
Product
reference
QTi DALI-T/E 1X18…57 DIM
1)
DALI / Touch DIM / Touch DIM Sensor
123
79
33
130
67
20
1
QTi DALI-T/E 2X18…42 DIM
1)
DALI / Touch DIM / Touch DIM Sensor
123
79
33
130
67
20
1
1) Optional cable clamp, see chapter ECG mountings - cable clamp
Product features
—
Very high efficiency
—
Line frequency: 0 Hz / 50 Hz / 60 Hz
—
Dimming range: 1…100 % (3…100 % with compact
fluorescent lamp)
—
Lifetime: up to 100,000 h
(temperature at T c = 65 °C, max. 10 % failure rate)
—
Very low standby power consumption:
< 0.2 W (A1 BAT)
—
Very high number of switching cycles: up to 300,000
—
Corridor function for direct connection of ECG to
common motion sensor
—
Corridor function with pre-programmed light
program
—
Touch DIM
®
function for free parameterization of light
value and turn on time
—
Feedback of consumed mains power and lamp
operating hours (Fit for SMART GRID)
—
Fit for Emergency function for automatic detection of
emergency lighting by ECG
—
POWER2LAMP function for optimal matching of
ECG power to lamp during lamp lifetime
Product benefits
—
Touch DIM
®
function for easy and inexpensive
dimming of several ECG
—
Automatic switch-on after change of lamp
—
Same luminous flux with direct and alternating
current
DALI product features
—
Control via the DALI interface
—
Compliance with the DALI standard to IEC 60929
and IEC 62386
—
Control input protected against overvoltage and
polarity reversal (OSRAM ECG)
Areas of application
—
Suitable for emergency light installations
—
Suitable for indoor installations