Стр. 457 - OSRAM_lamp_2014

Упрощенная HTML-версия

9.117
Installation and operating instructions
ECG
ECG
Maximum no. of
ECGs on circuit
breaker
10 A 16 A
Maximum no. of
ECGs on circuit
breaker
10 A 16 A
T H /μs
measured at
50 %
Ipeak
T H /μs
measured at
50 %
Ipeak
I P /A
I P /A
OPTOTRONIC
®
constant current - 700mA
OT 18/200-240/700 DIM
15
170
30
48
OPTOTRONIC
®
constant current 3DIM/DALI
OT 50/220-240/700 3DIMLT+E
25
250
9
18
OT 90/220-240/700 3DIMLT+E
40
330
6
12
OT 150/220-240/700 3DIMLT+E
58
360
4
9
OPTOTRONIC
®
constant voltage 12 V
OT 15/12 P
20
170
32
51
OT 30/12 P
30
170
13
21
OTe 60/110-277/12 E
15
200
7
12
40
200
7
12
OT 60/12 P
35
170
11
17
OTe 120/110-277/12 E
60
250
3
6
100
250
3
6
OT 120/12 P
40
300
6
10
OPTOTRONIC
®
constant voltage 24 V with DALI
OTi DALI 75/220-240/24 1…4CH
35.6
270
7
12
OPTOTRONIC
®
constant voltage 24 V with 1…10 V
OT 80/24 DIM P
35
360
7
10
OT 120/24 DIM P
60
250
6
10
OT 240/24 DIM P
70
250
5
8
OPTOTRONIC
®
constant voltage 24 V
OT 6/200-240/24 CE 15
240
30
48
OT 8/200-240/24
15
240
30
48
OT 20/220-240/24 10
100
25
41
OT 20/120-240/24 S 45
150
7
11
OT 30/220-240/24 P 23
270
13
21
OT 50/220-240/24 45
80
12
19
OT 50/220-240/24 P 22
270
12
19
OT 65/220-240/24 3DIM E
50
180
7
12
OT 75/220-240/24 41
200
7
12
OT 75/220-240/24 E 41
200
7
12
OT 80/220-240/24 P 35
360
7
10
OT 120/220-240/24 P
60
250
6
10
OTe 120/220-240/24 E
70
300
3
5
OT 240/220-240/24 P
70
250
5
8